Procedure for Preventive Maintenance of Level Transmitter (Type: GWR)
SCOPE
PROCEDURE:
2. Make sure all electrical
connections are tightened properly.
3. Check the housing seal for
any breakage.
4. Isolate the bridle by
closing its valves.
5. Open the drain valve and
completely flush the bridle.
6. Connect HART
communicator with the transmitter.
7. Observe the reading on
the local display and check 4 mA output.
8. Check the zero calibration
of the transmitter. If adjustment is required, apply ZERO trim command.
9. Close the drain valve,
fill the bridle up to 50% of its range, and observe the level through level
gauge glass.
10. Observe the reading on
the local display and check 12 mA output.
11. Verify 50% value on the
local display.
12. Fill the bridle
completely up to 100% of its range and observe the level through level gauge
glass.
13. Observe the reading on
the local display and check 20 mA output.
14. Verify 100% value on the
local display.
15. Now take the bridle into
service. Open low pressure side valve first and THEN the high-pressure side.
16. Disconnect HART
communicator from the transmitter.
17. Remove BYPASS mode from
the HMI.